SEM
Smart Energy Manager
Device Description
SEM is a compact and highly capable monitoring and control device for commercial, industrial and utility tbased energy management applications. It supports most of the common industrial communication protocols ( Modbus, IEC104, IEC62056 etc.) as well as those being used for IoT applications (REST, MQTT, CoAP etc.). Owing to its embedded click-on communication board, you can choose any type of media over GSM, Wi-fi, Ethernet, Zigbee or Lora. SEM’s power measurement feature provides monitoring of two three-phase circuits simultaneously with a sampling rate of 3.2kHz. Besides, it has an SD Card option up to 32GB to restore data even if there is a loss of communication. Its embedded and expandable digital inputs and outputs make it very easy to have more information from other communicable devices opening the door to a world of connectivity and control.
Device Specifications | |
Supply Voltage Range | 85 – 264 VAC |
Nominal Supply Voltage | 230VAC |
CPU | ARM Cortex-M4 32 Bit 96 Mhz |
Flash | 1mB |
RAM | 320 kB |
Watchdog Timer | System Reset / 5 sec |
Power Consumption | 2.3W @ 230 VAC |
Real Time Clock | Available |
Configuration | Web Server Interface / MCU-CX Configurator |
Wi-Fi Specifications | |
Wi-Fi Protocols | 802.11 b/g/n |
Frequency Range | 2.4 GHz – 2.5 GHz (2400M – 2483.5M) |
Wi-Fi Antenna | Extenal Antenna On board SMA Connector |
RF Certification | SRRC, FCC, CE (RED), IC, NCC, KCC, TELEC (MIC) |
Wi-Fi Certification | Wi-Fi Alliance |
Wi-Fi Mode | Station / SoftAP / SoftAP + Station |
Security | WPA / WPA2 |
Network Protocols | IPv4, TCP / UDP / HTTP / FTP |
GSM Specifications | |
Embedded GSM | Yes (Optional) |
Operating Frequencies | Standard (Quad Band GSM module 850/900/1800/1900 MHz) |
Number of Connections | 6 |
GSM Antenna | On Board SMA Connector |
Ping Blocking | Yes |
Stop Bit and Parity Bit Adjustment | Yes |
Identification With Phone Number | Yes |
Dispatch of warnings and alarms from software as text message to adminis-trators possible | Yes |
3G / 4G Connection | Optional |
Communication Specifications | |
Communication Protocols | Modbus-RTU (Slave), IEC60870-5-104, IEC62056-21 |
Serial Interfaces | RS-485, Micro USB C Type 2.0 |
RS-485 BaudRate | 1200bps – 115200bps |
USB Data Transfer Speed | 480 Mbit/s |
Power Measurement Specifications | |
Voltage Measurement Range | 0 – 275 VAC,RMS (L – N), 0 – 500 VAC,RMS (L – L) |
Current Measurement Range | 1 – 4000 AAC,RMS (Split Type) |
Frequency | 50 / 60 Hz ±5% |
Voltage Channels | 3P + N (3 Phase Voltage and Neutral) |
Current Channels | 2 x 3P (Either 2 x 3 Phases or 6 Single Phases) |
Sampling Frequency | 128 Sample / Cycle |
Voltage Accuracy | ±0,5% |
Current Accuracy | ±0,5% |
Active Energy Accuracy | IEC 62053-22 Class 0.5S Mbit/s |
Accuracy Class | IEC 61000-4-30 Class S |
Basic Measurements | V, I, f, P, Q, S / kWh, kVArh, kVAh (Four Quadrant) / PF, cos φ / THD-I, TDD-I, THD-U, THD-V / K-Factor / Ih(1-13) – Vh(1-13) |
Detailed Measurements | Outage / Maximum Voltage, Current and Power Demand |
Programmable Alarms | Under Voltage / Over Voltage / Low Current / High Current |